Engine accessories:

  • Heavy-duty air filter
  • Coolant heater
  • Lubricant oil heater
  • Fuel and Water Separator
  • Lube oil rotary pump

Alternator And Accessories:

  • Leroy somer/stamford
  • Anti condensation heater
  • PMG + AVR ◇ Double bearing
  • Alternator High voltage ______kV
  • RTDs for Bearing and winding

Cooling System:

  • 55 degree Radiator
  • Remote Radiator

Control System:

  • AMF
  • Parallel
  • Practical type in low temperature environment
  • Control Screen Heater
  • Remote Annunciators
  • Other(ComP, DEIF)

Circuit Breaker:

  • 3/4 poles
  • Fixed/handcart type
  • Electric mechanism

Automatic Transfer Switch (ATS):

  • ATS cabinet
  • Contractor type ATS
  • Motorized changeover type ATS

Start Battery:

  • Nickel-cadmium battery
  • Maintenance-free battery
  • Battery charger and selector switch
  • Charging current meter

External Fuel Tank:

  • Single /double wall fuel tank (500-5000 L)
  • Fuel Transfer pump

Exhaust Muffler:

  • Residential grade
  • Critical grade
  • Hospital grade

Available for voltages :

  • 400/230V, 480/277V, 380/220V, 440/254V, 416/240V,220/127V, 208/120V
Rent Now

Electrical Load Calculator

Lights

20W Tubelight
60W Light Bulb
100W Light Bulb
20W Energy Saver

Air Fans

21" LCD
DVD Player
Home Theater
Desktop PC
Laptop
Refrigerator
Freezer

Air Conditioners

1.5 Ton
2 Ton
2.5 Ton
3 Ton
3.5 Ton
4 Ton
4.5 Ton
5 Ton

Appliances

Fans
Air Coolers

Technical Specifications

Standard Specifications:

  1. 1- Prime Rating:Unlimited hours usage, with an average load factor of 80% over each 24 hour period. 10% overload is available for 1 hour in every 12 hours operation.
    0 overload is permitted on standby power.
  2. 2- Standby Rating:Limited to 500 hours annual usage, with an average load factor of 80% of the published standby power rating over each 24 hour period. Up to 300 hours of annual usage may be run continuously.
    No overload is permitted on standby power.
  3. 3- Engine:Perkins, including air filters, fuel filters, oil filter, starting motor and charging alternator etc.
  4. 4- Alternator Type:brushless AC alternator
  5. 5- Radiator:50°C, fan protective shroud
  6. 6– Fuel Tank:Capacity of fuel tank is for 8 hours running
    Built in fuel tank up to 800 kVA
  7. 7- Circuit Breaker:3 pole LS MCCB
  8. 8– Control system alarms:
    • Over and Under Speed
    • Low and High Battery Volt.
    • Start and Stop Failure
    • Over Current
    • Under / Over Generator Voltage
    • Low Oil Pressure
    • Emergency stop
    • High engine temperature
  9. 9– Warranty policy:
    • AQT Generator products has a warranty for 12 Months or 1000 hours whichever occurs first against any manufacturing defects
    • Wearing parts (filters), incorrect man made operation, maintenance failures are excluded from the warranty policy

Acoustic Enclosure Specifications:

 

Enclosure Type Acoustic & Weather Proof
Drainage Provision Fuel and Water Drainage
Transportation Tested Single Point Lifting
Facility & Forklift Pockets
Ingress Protection Rating IP 23
Lifting ISO Standard Lifting
Canopy RAL Color TAL 9010
Base frame RAL Color RAL 9011
Noise Pressure level @ 7m 66db(A) @ 7mt

Output Rating:

PRIME: STANDBY:
50 Hz—1500 Rpm 400 V, 3ph
45 kVA 36 kW
50 kVA 40 kW
60 Hz—1800 Rpm 480 V, 3ph
53.1 kVA 42.5 kW
58.7 kVA 46.9 kW
ENGINE SPECIFICATIONS
Engine Make PERKINS
Engine Model 1103 -33TG1
No. of Cylinders 3 vertical in-line
Cycle 4 Strokes
Aspiration Turbocharged
Cooling Method Water cooled
Governing Type Mechanical
Governing Class G2 – ISO 8528 Part 1
Compression Ratio 17.25:1
Displacement 3.3 L
Bore/Stroke 105 x 127 mm
Dynamic Charging Alternator 65AMP, 12V
ALTERNATOR SPECIFICATIONS
Alternator Make Leroy Somer | STAMFORD
Alternator Model TAL-042-F
Number of Poles 4
Number of Winding Leads 6
Type of Bearing Single Bearing
Insulation Class – Temp Rise Cont. H – 125/40̊ ̊C
Ingress Protection Rating IP 23
Excitation System Self Excited
AVR Model R120
Comply with Standards
ISO 3046, BS 5514, DIN 6271, NEMA-MGI, DIN EN, BS 5000, IEC 60034,IEC 60947-2
Alternator Operating Data
Over speed 2250 rpm
Voltage Regulation ± 1%
Harmonic Coefficient THF < 2%
Tel. influence TIF < 50
Cooling air flow 0.10 m3/ Sec

Engine:

Perkins heavy duty high performance industrial type diesel engine.

COOLING SYSTEM
Total Coolant Capacity (L) 10.2 L
Cooling Fan Air Flow 53 m3/ min
Radiator Fan Load 0.4 kW
Heat Radiation to Room (PRP) 7.0kW
Heat Radiation to Room (ESP) 8.0 kW
LUBRICATION SYSTEM
Oil Filter Type Spin-On Full Flow
Total Oil Capacity 8.3L
Oil Type API-CH-4 or ACEA E5
EXHAUST SYSTEM
Muffler Type Industrial Grade
Max. Back Pressure 10 kPa
Exhaust Gas Flow (PRP/ESP) 7.0/7.7 m3(PRP/ESP) / min
Exhaust Gas Temperature < 551C
FUEL SYSTEM
Recommended Fuel Class A2 Diesel
Fuel Consumption Standby 11.70 L/hr
Fuel Consumption 100% PRP 10.80 L/hr
Fuel Consumption 75% PRP 8.23 L/hr
Fuel Consumption 50% PRP 5.83 L/hr
AIR SYSTEM
Air Filter Type Dry Element
Combustion Air Flow (PRP) 2.9 m3/min
Combustion Air Flow (ESP) 3.1 m3/min
Max Air Filter Intake Restriction 8 kPa

Control System:

  • Large back-lit text display
  • Multiple display languages
  • DSENET expansion compatible
  • Data logging facility
  • Fully configurable via PC using USB communication
  • Front panel configuration
  • Efficient power save mode
  • 3 phase generator sensing
  • Accumulated power monitoring (kWh, kVA h, kVAr h)
  • Generator/load current monitoring and protection (kW)
  • Breaker contol via fascia buttons
  • Fuel and start outputs, configurable using can
  • 4 configurable DC outputs
  • 4 configurable analogue/digital inputs
  • Automatically transfers between mains (utility) and generator
  • Increased input and output expansion capability via dsenet
  • IP65 rating (with optional gasket) offers increased resistance to water ingress
  • Digital inputs; Analogue Inputs
Dimensions:
Type Length
(mm)
Width
(mm)
Height
(mm)
Fuel Tank
( L )
Weight
(KG)
OPEN 1950 775 1175 100 850